Liqui-Mover® Pressure-Powered Pump
First introduced in 1934, the Liqui-Mover pump is a pressure-powered pump that performs the same liquid transport functions as centrifugal pumps. However, the Liqui-Mover pump is based on an entirely different operating concept and has fewer moving parts than conventional centrifugal pumps.
The positive displacement condensate pump has no motors, starters, rotating shafts, mechanical seals or impellers. Instead, it uses steam or compressed air as the motive force to lift or pump liquids.
With no maintenance-intensive components to leak, wear, or fail, the Liqui-Mover condensate pump is a naturally more reliable than conventional pumps. As a result, the Liqui-Mover condensate pump will work longer, with less maintenance and far less downtime than conventional pumps.
What to look for when choosing a pump for steam condensate service
- Ability to handle high temperature condensate and flash steam
- Energy efficiency
- Low maintenance
- Proven performance and reliability
| Parameter | Electric Centrifugal Condensate Pumps | Liqui-Mover Pressure-Powered Condensate Pump |
|---|---|---|
| Maximum Condensate Temperature | 200° F | 365° F |
| Energy Efficiency | Sized with 2:1 safety factor | Sized for actual incoming load |
| Electricity | Required | Optional |
| Additional Flash Tank | Required | Optional |
| Rotating Parts | Seal kits, motors, impellers | None |
| Insulated Pump & Receiver | No | Yes |
| Zero Flash System | No | Yes |
| Pumping Loads & Backpressure | Low | High |
| Ease of Repair | Low | High |
Float Level Control |
Float-Free Level Control |
Replacement Level Control |
| The float operated Liqui-Mover condensate pump requires no electricity and is available as a complete skid-mounted assembly or as individual components for field assembly. | The float-free Liqui-Mover condensate pump uses a conductance level control system with capacities up to 89,000 pounds per hour for a single pump. Float-free designs are available as a skid-mounted assembly or as individual components for field assembly. | Replacement level controls are a reliable and cost-effective solution for pressure-powered pumps and pumping systems. Designed to retrofit major float-actuated pumps brands, both the float and float-free assemblies feature a bolt-on mounting flange. |